15
ENVIRONMENTAL CONDITIONS
Operating temperature between -15°C and +60°C (+5°F and +140°F)
Storage temperature between -25°C and +75°C (-13°F and +167°F)
Relative humidity 80% max without condensation
MECHANICAL CHARACTERISTICS
Material plastic enclosure - noryl UL94-V0
Protection degree IP51 (front panel); IP20 (terminals)
Terminals conductors 2.5mm
2
Size / Weight 106 x 90 x 57mm, 6 DIN-RAIL modules, 300gr
STANDARDS COMPLIANCE
Safety 73/23/EEC and 93/68/EEC directives, EN61010.1 safety standard
EMC 89/366/EEC directive and following modifications 93/31/EEC and 93/68/
EEC, EN50081-2, EN50082-2, EN61326/A1
INSTANTANEOUS MEASUREMENTS
PHASE VOLTAGE * V
1
- V
2
- V
3
[V]
LINE VOLTAGE V
12
- V
23
- V
31
[V]
SYSTEM VOLTAGE V [V]
LINE CURRENT * & NEUTRAL CURRENT * I
1
- I
2
- I
3
- I
N
[A]
SYSTEM CURRENT I [A]
POWER FACTOR * PF
1
- PF
2
- PF
3
SYSTEM POWER FACTOR PF
APPARENT POWER * S
1
- S
2
- S
3
[VA]
SYSTEM APPARENT POWER S [VA]
ACTIVE POWER * P
1
- P
2
- P
3
[W]
SYSTEM ACTIVE POWER P [W]
REACTIVE POWER * Q
1
- Q
2
- Q
3
[var]
SYSTEM REACTIVE POWER Q [var]
FREQUENCY f [Hz]
PHASE REVERSAL 123 / 132
DEMAND VALUES 4xI
DMD
- S
DMD
- P
DMD
STORED DATA
SYSTEM ACTIVE ENERGY [Wh]
SYSTEM APPARENT ENERGY [VAh]
SYSTEM LAGGING REACTIVE ENERGY [varh ind]
SYSTEM LEADING REACTIVE ENERGY [varh cap]
PEAK VALUES 3xV
L-N
- 3xV
L-L
- 3xI
L
- 3xI
DMD
- P
DMD
- S
DMD
= Standard = Optional = Bi-directional value (BIDIR option only)
* Parameters not available in case of 3-3-3 connection.