All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014 15
Bulletin 1606 Switched Mode Power Supplies
16. Protection Features
Output protection Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ. 58.5Vdc
max. 60Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection IP 20 EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.
Penetration protection > 5mm e.g. screws, small parts
Over-temperature protection yes Output shut-down with automatic restart
Input transient protection MOV (Metal Oxide Varistor)
Internal input fuse included not user replaceable
*) In case of a protection event, audible noise may occur.
17. Safety Features
Input / output separation
*)
SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5MOhm input to output, 500Vdc
PE resistance < 0.1Ohm
Touch current (leakage current) typ. 0.14mA / 0.37mA 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.20mA / 0.55mA 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.35mA / 0.87mA 230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.17mA / 0.46mA 110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.26mA / 0.67mA 132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.46mA / 1.08mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation