All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
Do not operate this power supply with DC-input voltage. Use the 1606-XLE480FP-D instead.
5. Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current
*)
max. 13A
peak
13A
peak
13A
peak
temperature independent
typ. 11A
peak
9A
peak
7A
peak
temperature independent
Inrush energy
*)
max. 2A
2
s 2.5A
2
s 0.5A
2
s temperature independent
Inrush delay typ. 940ms 940ms 740ms start-up delay plus rise time
*) Mains interruptions > 500ms