22 Compact I/O High-speed Counter Module
Publication 1769-IN030B-EN-P - October 2010
Module Powerup
At module powerup, a series of internal diagnostic tests are
performed. These diagnostic tests must be successfully completed or
the module OK status indicator remains off or red, and a module
error is reported to the controller.
Diagnostic Indicators
Default Configuration
When the module is powered up for the first time, it uses the following default configuration
values. All counters are disabled and all outputs are off. The module’ s Default Safe State
configuration is all zeros, resulting in the following:
Program State = UDSS (user-defined safe state)
Program Value = OFF
ProgramStateRun = No
Fault State = UDSS (user-defined safe state)
Fault Value = OFF
FaultStateRun = No
PFE (Program to Fault Enable) = leave program value applied.
Refer to the Compact I/O High-speed Counter User Manual, publication 1769-UM006
, and
use your programming software to change the configuration.
Status
Indicator
Color Indicates Status
Indicator
Color Indicates
0 OUT Amber ON/OFF logic status of output 0 A0 Amber ON/OFF status of input A0
1 OUT Amber ON/OFF logic status of output 1 A1 Amber ON/OFF status of input A1
2 OUT Amber ON/OFF logic status of output 2 B0 Amber ON/OFF status of input B0
3 OUT Amber ON/OFF logic status of output 3 B1 Amber ON/OFF status of input B1
FUSE Red Overcurrent Z0 Amber ON/OFF status of input Z0
OK Off No power is applied Z1 Amber ON/OFF status of input Z1
Red (briefly) Performing self-test
Solid green Normal operating condition
Flashing green OK, in Program or Fault mode
Solid red or
amber
Hardware error. Cycle power to the module. If problem persists, replace
the module
Flashing red Recoverable fault. Reconfigure, reset, or perform error recovery. Refer to the
Compact I/O High-speed Counter User Manual, publication 1769-UM006
ALL ON Possible causes for all status indicators to be On include the following:
Bus error has occurred: Controller hard fault. Cycle power.
During upgrade of controller: Normal. Do not cycle power during the upgrade.
02
1
OK
3
A0 Z0B0
OUT
IN
A1 Z1
B1
FUSE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1769-HSC and is the answer not in the manual?

Allen-Bradley 1769-HSC Specifications

General IconGeneral
BrandAllen-Bradley
Model1769-HSC
CategoryI/O Systems
LanguageEnglish

Related product manuals