20    FLEX I/O Digital Input Modules 
Publication 1794-IN093E-EN-P - August 2018
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), 
IEC 60068-2-2 (Test Bd, Operating Dry Heat), 
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °C) – 1794-IB8, 1794-IB16 
0…55 °C (32…131 °F) – 1794-IB32
Temperature, surrounding air, 
max.
55 °C (131 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), 
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), 
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g
Emissions IEC 61000-6-4
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
(1794-IB8, 1794-IB16)
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz  
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
(1794-IB32)
10V/m with 1 kHz sine-wave 80% AM from 80...1000 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV @ 5 kHz on power ports 
±2 kV @ 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz