Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 59
Programming and Parameters Chapter 3
b007 [Fault 1 Code] Related Parameter(s): A186
, A197, d307...d315
A code that represents a drive fault. [Fault 1 Code] is the most recent fault. Repetitive faults will only be recorded once.
Refer to Chapter 4
for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
b008 [Process Display] Related Parameter(s): b001, A160
32 bit parameter.
Output frequency scaled by A160 [Process Factor]
Values Default: Read Only
Min/Max: 0.00/9999
Display: 0.01 – 1
32
Output
Freq
Process
Display
Process
Factor
x=
b010 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.0/999.9 kW
Display: 0.1 kW
b011 [Elapsed MWh] Related Parameter(s): b015, A195
Accumulated output energy of the drive.
Values Default: Read Only
Min/Max: 0/3276.7 MWh
Display: 0.1 MWh
b012 [Elapsed Run Time] Related Parameter(s): A195
Displays the accumulated time that the drive has output power since the last A195 [Reset Meter].
Time is displayed in 10 hour increments.
Values Default: Read Only
Min/Max: 0/9999 Hrs
Display: 1 = 10 Hrs
b013 [Torque Current]
Displays the torque portion of the output current.
Values Default: Read Only
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
b014 [Drive Temp]
Present operating temperature of the drive power section.
Values Default: Read Only
Min/Max: 0/120 degC
Display: 1 degC