12 ControlLogix DC (10-30V) Sourcing Input Module
Publication 1756-IN006A-EN-P - December 2000
Remove the Module
1756-IV16 Specifications
Number of Inputs 16 (8 points/common)
Module Location 1756 ControlLogix Chassis
Backplane Current 110mA @ 5.1V dc & 2mA @ 24V dc
(Total backplane power 0.61W)
Maximum Power Dissipation
(Module)
5.41W @ 60
o
C
Thermal Dissipation 18.47 BTU/hr
On-State Voltage Range 10-30V dc
Nominal Input Voltage 24V dc
On-State Current 2.0mA @ 10V dc minimum
10mA @ 30V dc maximum
Maximum Off-State Voltage 5V
Maximum Off-State Current 1.5mA
Maximum Input Impedance
@ 30V dc
3.2k
Input Delay Time
OFF to ON
Hardware delay
ON to OFF
Hardware delay
Programmable filter: 0ms, 1ms or 2ms
1ms maximum plus filter time
Programmable filter: 0ms, 1ms, 2ms, 9ms or 18ms
2ms maximum plus filter time
Diagnostic Functions
Change of State
Timestamp of Inputs
Software configurable
+/- 200µs
Maximum Inrush Current 250mA
Cyclic Update Time User selectable (100µs minimum/750ms maximum)
Reverse Polarity Protection Yes
1. Push in top and bottom locking tabs. 2. Pull module out of the chassis.
20856–M 20857–M