EasyManua.ls Logo

Allen-Bradley PanelView Plus 400

Allen-Bradley PanelView Plus 400
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 PanelView Plus and PanelView Plus Compact 400 and 600 Terminals
Publication 2711P-IN002G-EN-P - November 2009
Hazardous Locations
This equipment is suitable for these locations:
Class I, Division 2 Groups A, B, C, D
Class II, Division 2 Groups F, G
Class III
Ordinary non-hazardous locations only
The following statement applies to use in hazardous locations.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum
ambient temperature. Do not install the terminals in environments where atmospheric gases
have ignition temperatures less than 135 °C (275 °F).
WARNING
Explosion Hazard
Substitution of components may impair suitability for hazardous locations.
Do not disconnect equipment unless power has been switched off and area is
known to be non-hazardous.
Do not connect or disconnect components unless power has been switched off.
All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section
18-1J2 as appropriate.
Peripheral equipment must be suitable for the location in which it is used.

Other manuals for Allen-Bradley PanelView Plus 400

Related product manuals