Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 27
Fault Messages Chapter 1
X Inv General Flt 671 Inverter general fault: The SGCTs have passed their
operational lifetime and maintenance needs to be completed.
Verify the LV connections and configuration of the input device feedback to the OIBBS.
Verify the drive configuration
Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement.
X Inv Heartbeat 132 The master processor has detected that the slave DSP
software has either over-run or failed to initialize.
Verify DC Control voltages on ACB.
Cycle power and replace DPM board if necessary.
X X X InvHS TempSensor 503 The specified temperature reading is out of normal range. Verify that bit-1 of parameter P274 is set correctly.
Ensure that the temperature sensor is correctly plugged in and is not damaged.
X Inv InpCtctrClsd 689 Inverter input contactor closed
: The safety control system has
detected a fault in the drive input contactor control system.
The input device indicates closed when it was commanded to
open by the OIBBS.
Verify the input contactor. In case the contactor has any problem(s), stop running the drive
and contact the manufacturer.
Verify the low voltage wiring of the input contactor / circuit breaker control command.
Verify the low voltage wiring of input contactor feedback.
Cycle the control power.
X Inv NSR PS Rng 668 Inverter non safety-related power supply out of range: The
inverter OIBBS diagnostic subsystem has detected an out of
range power supply voltage of the 24Vdc power supply.
Verify the STO system power supply/connection to the OIBBS.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for spare parts of the power
supply and/or OIBBS for replacement.
X Inv OIB Detected 688 Inverter OIB detected
: The safety control system has detected
incompatible hardware. One or more OIBs have been
detected.
Verify the board mounted on the inverter OIBBS. It should be OIB2, not OIB.
In case OIB(s) is/are applied, contact the manufacturer for the OIB2 spare parts for
replacement.
X Inv OvrVoltage 160 The inverter output voltage given by Inv Output Volt (P761)
has exceeded the trip settings. This is detected by the
hardware circuit in the ACB.
This is drive output Voltage [ESP Surface Volt (P760) terminology used in ESP application].
The protection uses P193 setting but drive calculates the motor filter cap voltage.
In ESP application Inverter voltage may be different from motor voltage due to long cable
drop.
Check the voltage sensing board for any resistor failure.
Check for any open circuit at the drive output.
Check the devices at the inverter.
X Inv PS Out Rng 666 Inverter power supply out of range: The inverter OIBBS
diagnostic subsystem has detected an out of range power
supply voltage on the internally generated supplies.
Verify the STO system power supply/connection to the OIBBS.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for spare parts for the
power supply and/or OIBBS for replacement.
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Fault Message Fault Code Description Recommended Action(s)