28 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 1 Fault Messages
X Inv PSD Fault 690 Inverter power structure diagnostic fault: The safety control
system has detected a fault in one or more SGCTs. Incorrect
SGCT unit feedback was detected.
Resolve all other faults first
Ensure there are OIB2s are installed in the OIBBS, not the OIBs
Ensure proper configuration setting of the SPS with drive hardware
Check the LV wiring from the input device feedback
Check the LV wiring/connectors to the OIBBS and ACB.
Verify correct STO configuration settings
Turn off all the power supplies to the drive and replace the SGCTs according to the
procedures in the User Manual.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part(s)
for replacement.
X Inv S1 Stuck 672 Inverter S1 stuck: The inverter OIBBS diagnostic subsystem
has detected a fault.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Inv S2 Stuck 673 Inverter S2 stuck
: The inverter OIBBS diagnostic subsystem
has detected a fault.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Inv S3 Timeout 676 Inverter S3 timeout: The inverter OIBBS diagnostic subsystem
has detected a fault. A problem of timing function on the
OIBBS has been detected.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Inv STOInp Invld 675 Inverter safety input invalid: The inverter OIBBS diagnostic
subsystem has detected an invalid control input state.
Verify the wiring of the inverter OIBBS.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Inv Temp Out Rng 667 Inverter temperature out of range
: The inverter OIBBS
diagnostic subsystem has detected an out of range
temperature.
Verify the airflow in the low voltage control compartment.
Shut off the control power to let the temperature in the control compartment cool.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X X X Inv TFBFbk Error 499 The drive has lost the fiber-optic signal from the specified
temperature feedback board.
Verify that bit-1 of parameter P274 is set correctly.
Check for damaged fiber-optic cable or loose connection.
X Inv WtchDg T Out 665 Inverter watchdog timeout: A failure of the Inverter OIBBS
diagnostic subsystem was detected.
Verify all the connections for OIBBS, OIB2 on inverter side.
This fault will only reset upon cycling control power.
Cycle the control power, and if the same fault still trips the drive, contact the manufacturer
for spare parts of the OIBBS, OIB2 and/or the connections for replacement.
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Fault Message Fault Code Description Recommended Action(s)