24 Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 1 Installation/Wiring
Fuses and Circuit Breakers for PowerFlex 520-Series Drives (continued)
200...240V 3-Phase Input Protection Devices – Frames A...E
(1) Normal Duty (ND) and Heavy Duty (HD) ratings are available for this drive.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(4) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 480Y/277 and 600Y/347 AC input. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(6) When using a Manual Self-Protected (Type E) Combination Motor Controller with this drive power rating, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.
Catalog No.
(1)
Output Ratings Input
Ratings
Frame Size
Contactor
Catalog No.
IEC Applications (Non-UL) UL Applications
PF 523 PF 525 ND HD
Amps
kVA
Max
Amps
(2)
Fuses (Rating) Circuit Breakers Fuses (Max. Rating) Circuit Breakers Min.
Enclosure
Vol. (in.
3
)
HP kW HP kW Min. Max. 140U/140G 140M Class / Catalog No. 140U/140G 140M
(3)(4)(5)
25A-B1P6N104 – 0.25 0.2 0.25 0.2 1.6 0.9 1.9 A 100-C09 3 6 140U-D6D3-B30 140M-C2E-B25 CLASS RK5, CC, J, or T / DLS-R-15 140U-D6D3-B30 140M-C2E-B25 –
25A-B2P5N104 25B-B2P5N104 0.5 0.4 0.5 0.4 2.5 1.2 2.7 A 100-C09 6 6 140U-D6D3-B40 140M-C2E-B40 CLASS RK5, CC, J, or T / DLS-R-6 140U-D6D3-B40 140M-C2E-B40 –
25A-B5P0N104 25B-B5P0N104 1.0 0.75 1.0 0.75 5.0 2.7 5.8 A 100-C09 10 16 140U-D6D3-B80 140M-C2E-B63 CLASS RK5, CC, J, or T / DLS-R-15 140U-D6D3-B80 140M-C2E-B63 –
25A-B8P0N104 25B-B8P0N104 2.0 1.5 2.0 1.5 8.0 4.3 9.5 A 100-C12 16 20 140U-D6D3-C10 140M-C2E-C10 CLASS RK5, CC, J, or T / DLS-R-20 140U-D6D3-C10 140M-C2E-C10 –
25A-B011N104 25B-B011N104 3.0 2.2 3.0 2.2 11.0 6.3 13.8 A 100-C23 20 32 140U-D6D3-C15 140M-C2E-C16 CLASS RK5, CC, J, or T / DLS-R-30 140U-D6D3-C15 140M-C2E-C16 –
25A-B017N104 25B-B017N104 5.0 4.0 5.0 4.0 17.5 9.6 21.1 B 100-C23 32 45 140U-D6D3-C25 140M-F8E-C25 CLASS CC, J, or T / 45 140U-D6D3-C25 140M-F8E-C25 –
25A-B024N104 25B-B024N104 7.5 5.5 7.5 5.5 24.0 12.2 26.6 C 100-C37 35 63 140G-G6C3-C35 140M-F8E-C32 CLASS CC, J, or T / 60 – 140M-F8E-C32 –
25A-B032N104 25B-B032N104 10.0 7.5 10.0 7.5 32.2 15.9 34.8 D 100-C43 45 70 140G-G6C3-C60 140M-F8E-C45 CLASS RK5, CC, J, or T / DLS-R-70 – 140M-F8E-C45 –
25A-B048N104 25B-B048N104 15.0 11.0 10.0 7.5 48.3 20.1 44.0 E 100-C60 63 90 140G-G6C3-C70 140M-F8E-C45 CLASS CC, J, or T / 90 – 140M-F8E-C45 1416.0
(6)