EasyManua.ls Logo

Allen-Bradley powerflex 700 - Page 90

Allen-Bradley powerflex 700
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-62 Digital Inputs
PowerFlex 700 Digital Input Selection
INPUTS & OUTPUTS
Digital Inputs
361
362
363
364
365
366
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
(11)
Selects the function for the digital inputs.
(1)
Speed Select Inputs.
To access Preset Speed 1, set [Speed
Ref x Sel] to “Preset Speed 1”.
Type 2 Alarms - Some digital input
programming may cause conflicts
that will result in a Type 2 alarm.
Example: [Digital In1 Sel] set to “5,
Start” in 3-wire control and [Digital
In2 Sel] set to 7 “Run” in2-wire.
Refer to User Manual for information
on resolving this type of conflict.
(2)
Vector Control Option Only.
Default:
Default:
Default:
Default:
Default:
Default:
Options:
4
5
18
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-17
18
19
20
21
22
23
24
25
26
27
28
29
30
31-33
34
“Stop – CF”
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Not Used”
“Enable”
(8)(10)
“Clear Faults”(CF)
(4)
“Aux Fault”
“Stop – CF”
(10)
“Start”
(5)(9)
“Fwd/ Reverse”
(5)
“Run”
(6)(10)
“Run Forward”
(6)
“Run Reverse”
(6)
“Jog”
(5)
“Jog1”
(2)(5)
“Jog Forward”
(6)
“Jog Reverse”
(6)
“Stop Mode B”
“Bus Reg Md B
“Speed Sel 1-3”
(1)
“Auto/ Manual”
(7)
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
“Precharge En”
“Spd/Trq Sel1-3”
(2,3)
“Jog 2”
(2)
100
156
162
096
140
194
380
384
388
124
(4)
When [Digital Inx Sel] is set to option 2 “Clear Faults” the Stop button cannot
be used to clear a fault condition.
(5)
Typical 3-Wire Inputs - Requires that only 3-wire functions are chosen.
Including 2-wire selections will cause a type 2 alarm.
(6)
Typical 2-Wire Inputs - Requires that only 2-wire functions are chosen. Includ-
ing 3-wire selections will cause a type 2 alarm. See User Manual for conflicts.
(7)
Auto/Manual - Refer to User Manual for details.
(8)
Opening an “Enable” input will cause the motor to coast-to-stop, ignoring any
programmed Stop modes.
(9)
A “Dig In ConflictB” alarm will occur if a “Start” input is programmed without a
“Stop” input.
(10)
Refer to the Sleep-Wake Mode Attention statement on User Manual .
(11)
A dedicated hardware enable input is available via a jumper selection. Refer
to User Manual for further information.
3 2 1 Auto Reference Source
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
(3)
321Spd/Trq Mode
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Zero Torque
Spd Reg
Torque Reg
Min Spd/Trq
Max Spd/Trq
Sum Spd/Trq
Absolute
Zero Trq

Table of Contents

Other manuals for Allen-Bradley powerflex 700

Related product manuals