What to do if Allen-Bradley Controller shows Motor Overload?
D
Dakota LewisAug 13, 2025
If the Allen-Bradley Controller displays a 'Motor Overload' message, it indicates that the motor load is excessive. Reduce the load to ensure the drive output current does not exceed the current set by [Motor NP FLA].
A
Aaron FowlerAug 17, 2025
Why does my Allen-Bradley powerflex 700 show OverVoltage?
D
Darrell MillerAug 17, 2025
The Allen-Bradley Controller might show an 'OverVoltage' error due to high AC line voltage or transient conditions. It can also be caused by motor regeneration. To address this, monitor the AC line, extend the deceleration time, or install a dynamic brake option.
A
amylopezAug 20, 2025
What causes HW OverCurrent in Allen-Bradley powerflex 700 Controller and how to fix it?
N
Nathan MontgomeryAug 20, 2025
The 'HW OverCurrent' error in your Allen-Bradley Controller can be caused by programming issues, excessive load, an improper DC boost setting, or DC brake volts set too high, among other factors leading to excess current. Check these settings and conditions to resolve the issue.
B
brownkyleAug 25, 2025
What causes SW OverCurrent in Allen-Bradley Controller?
K
Katherine HoffmanAug 26, 2025
The 'SW OverCurrent' in Allen-Bradley Controller can be triggered by excess load, an improper DC boost setting, or excessively high DC brake volts. Check these settings.
M
Michael HigginsAug 28, 2025
How to fix OverSpeed Limit on Allen-Bradley Controller?
K
kortizAug 28, 2025
To resolve an 'OverSpeed Limit' issue on your Allen-Bradley Controller, remove any excessive load or overhauling conditions. Alternatively, increase the [Overspeed Limit] parameter.
M
Melissa GarzaSep 1, 2025
How to fix FluxAmpsRef Rang error on Allen-Bradley Controller?
J
jmejiaSep 1, 2025
To fix the 'FluxAmpsRef Rang' error on your Allen-Bradley Controller:
1. Reprogram [Motor NP FLA] with the correct motor nameplate value.
2. Repeat Autotune.
C
Cory GreenSep 5, 2025
What to do for Decel Inhibit on Allen-Bradley powerflex 700 Controller?
J
Jill SalasSep 5, 2025
To address 'Decel Inhibit' on an Allen-Bradley Controller:
1. Verify the input voltage is within the drive's specified limits.
2. Ensure the system ground impedance follows proper grounding techniques.
3. Disable bus regulation, add a dynamic brake resistor, or extend the deceleration time.
4. Disable the function with parameter 238.
S
swilliamsonSep 8, 2025
What does TB Man Ref Cflct mean on Allen-Bradley powerflex 700 Controller?
K
Katie MillsSep 8, 2025
The 'TB Man Ref Cflct' error on the Allen-Bradley Controller occurs when “Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and [TB Man Ref Sel], parameter 96 has been reprogrammed, meaning no other use for the selected analog input can be programmed. You can resolve this by either verifying/reprogramming the parameters that reference an analog input or reprogramming [Digital In3] to another function or “Unused.”