Rockwell Automation Publication 750-RM003A-EN-P - April 2018 7
Preface
Compatibility Quick Check
Use the following comparison table to confirm that there are compatible 
PowerFlex 755TM bus supplies available to migrate from your existing 
PowerFlex 700AFE bus supply. If the existing PowerFlex 700AFE installation 
configuration does not have any of these exceptions, proceed to use the 
guidelines in this document.
If the existing PowerFlex 700AFE bus supply has any of the above 
configuration exceptions, contact an Authorized Rockwell Automation 
Distributor specialist, Solution Partner, Recognized System Integrator, or 
Rockwell Automation account manager to discuss engineered solutions for 
custom migrations.
Follow this link for a list of Solution Partners and Recognized System 
Integrators: http://www.software.rockwell.com/corporate/sp/
RASISearchResults.cfm?Programlevel=SP.
Table 1 - Comparison Quick Check Considerations
Consideration If you have these existing PowerFlex 
700AFE Configuration Exceptions
Then follow these recommendations 
for the PowerFlex 755TM Bus Supply 
migration
Maximum DC bus 
current and power 
output
More than 2 x frame 13 AFE bus supplies in 
parallel.
When this migration guide was published 
there were no compatible units available. 
Future product enhancements may expand 
the range of migration solutions.
Mixed Frame Sizes Any combination of frame 10 and frame 13 
AFE converters in parallel.
Mixed frame parallel migration solutions 
are not covered in this migration guide. A 
custom migration solution may be 
required. 
Custom Packaging IP00 open type units that are installed in non-
standard enclosures.
Open type IP00 PowerFlex 755TM Bus 
Supplies are available. IP00 conversions are 
not covered in this migration guide. A 
custom migration solution may be 
required. 
Parallel non-
regenerative bus 
supply
Any system with an AFE in parallel with a 
non-regenerative converter (diode or SCR 
rectifier). The most common configuration 
was an AFE in parallel with PowerFlex SCR 
converter(s).
The PowerFlex 755TM Bus Supply cannot be 
combined in parallel with any other bus 
supply converters. 
Integration with 
common DC bus 
drive system lineup
DC bus bars, control bus bars integrated 
between the AFE and common bus inverter 
drive enclosures.
This configuration can be migrated to 
PowerFlex 755TM bus supply, however, this 
solution is not covered in this migration 
guide.
The IP21/IP54 enclosed PowerFlex 755TM 
bus supply converter bus bar configuration 
is not mechanically compatible with any 
existing PowerFlex 700AFE configurations 
and may require a custom migration 
solution with transition cell enclosure(s).
Communication 
Protocol
ControlNet Fiber
BACnetIP
HVAC Modbus RTU
CANopen
Interbus
LonWorks
Modbus/TCP
Remote I/O
RS485 DF1
These communication protocols are not 
supported by the PowerFlex 755T product. 
A custom migration solution and/or an 
external communication protocol converter 
may be required.