EasyManua.ls Logo

Alpha Technologies APP 9015S - Page 19

Default Icon
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Trouble-Shooting
19
© 2002
TM
016-537-B0-002 Rev. B
3.1 Trouble-Shooting Guide, Continued
Symptom #3:
Incorrect output voltage; And/or Ammeter reads excessive current (above rated output of APP
SPS):
Probable Cause:
60/75/90 VAC switch in wrong position
Wrong type of voltmeter used
Under-loaded output (less than 1 Amp)
Overloaded output
Short exists in load
MOV shorted in SPI
APP 9015S only: 120/240 V switch in
wrong position
Solution:
Move switch to required position
Use true RMS voltmeter
Connect load
Reduce load
Locate and remove short
Replace SPI
Set switch to correct line voltage