5
C048-699-30 R03, Rev. B (01/2021)
1.0 1.0 Purpose and ApplicabilityPurpose and Applicability
This document covers the installation and operation of the DCX
Series top terminal battery disconnect system.
1.1 1.1 Product ModelProduct Model
This document applies to Alpha products in the following model congurations:
Table 1. DCX Model Congurations - Switch Only Versions (No Current Limiting)
DESCRIPTION PART NUMBER
400A DCX Battery Disconnect; -48VDC; w/shunt C016-1001-10
600A DCX Battery Disconnect; -48VDC; w/shunt C016-1003-10
800A DCX Battery Disconnect; -48VDC; w/shunt C016-1005-10
1000A DCX Battery Disconnect; -48VDC; w/shunt C016-1007-10
1200A DCX Battery Disconnect; -48VDC; w/shunt C016-1009-10
Table 2. DCX Model Congurations - Magnetic Trip Versions
DESCRIPTION PART NUMBER
400A DCX Battery Disconnect; -48VDC; w/shunt C016-198-10
600A DCX Battery Disconnect; -48VDC; w/shunt C016-195-10
800A DCX Battery Disconnect; -48VDC; w/shunt C016-199-10
1000A DCX Battery Disconnect; -48VDC; w/shunt C016-196-10
1200A DCX Battery Disconnect; -48VDC; w/shunt C016 -207-10
For a list of mounting kit and accessory part numbers, refer to Section 6 on Page 17.
2.0 2.0 Theory of OperationTheory of Operation
The DCX disconnect product family includes multiple amperage ratings and installation mounting schemes to provide a
DC or Battery source disconnect device for use in Telecom +24 or -48VDC systems as well as solar-alternate energy
or other DC applications. The primary application for the DCX system is to provide over-current protection for battery
sourced equipment and wiring. The secondary function is to provide a service disconnect in order to maintain batteries or
to shut down the battery source connection in an emergency.
2.1 2.1 Circuit Breaker Trip RatingsCircuit Breaker Trip Ratings
The DCX product family includes circuit breaker trip ratings of 400, 600, 800, 1000, and 1200A. The electrical
conguration allows for both positive and negative connected systems as factory congured options. The DCX system
includes a circuit breaker or switch, an internal input and output copper bus structure, a steel inner housing, a circuit
board, and a ame retardant plastic outer housing.
2.2 2.2 Mounting CongurationsMounting Congurations
Several di󰀨erent mounting bracket option kits provide battery top terminal mounting congurations for numerous battery
manufacturer's cell congurations.