EasyManua.ls Logo

Alpha InTec2 28XE - Air Flow, Combustion, and Lighting

Alpha InTec2 28XE
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Alpha InTec² 25X Eand 28XE - Commissioning
5.4 CHECK THE AIR FLOW THROUGH THE HEAT EXCHANGER
The following air flow check must be carried out and the reading logged in the box provided in the table below. This figure is
then used as a reference during future servicing of the boiler to determine if the heat exchanger needs to be cleaned.
This check must be carried out with the front case fitted.
Before carrying out this check the flue must be fully installed and the condensate trap filled with water.
1. Remove the pressure test point caps at the top of the boiler and connect a digital differential pressure gauge across the
positive (F+) and negative (A-) pressure connections, see Fig. 5.3.
2. Set the boiler to stand by and press and hold the reset and stand by buttons simultaneously for 15 seconds. The
summer/winter symbol (
) and the number 55 will flash on the display indicating that the fan is running at a fixed
speed of 5500 rpm.
Note: The boiler does not fire during this operation.
3. Observe the pressure differential reading and compare it to the tables below and record the figure in the box at the
bottom of the table to be used as a reference for future servicing.
If on a future service the pressure reading has reduced by 40% or more then the heat exchanger must be cleaned.Refer to
Section 6.5.
i.e. If the measured value is less than 0.6 x the original reference value, the heat exchanger should be inspected and cleaned.
4. If during first commissioning the readings are not within those stated in the tables above then the flue must be checked
for integrity and length. If the flue length exceeds 5 m then the 'F0' parameter should be changed to suit, see parameter
settings in Section 5.14.
Note: If the 'F0' parameter has been changed then a fast calibration is required see Section 5.13. This is indicated by
the code E72 shown on the display.
The air flow check function will operate for 15 minutes, alternatively disconnect the boiler electrical supply or press the
standby button
for 8 seconds to exit the function early.
InTec² 25XE
InTec² 28XE
'F0' parameter setting
0
1
2
Recorded pressure
reading
Pressure (mbar)
0 to 1.68
1.68 to 2.02
2.02 to 2.40
Indicative flue length (m)
From 0 to 4.5
From 4.5 to 9.0
From 9.0 to 13.0
'F0' parameter setting
0
1
2
Recorded pressure
reading
Pressure (mbar)
0 to 1.58
1.58 to 1.81
1.81 to 2.02
Indicative flue length (m)
From 0 to 4.5
From 4.5 to 9.0
From 9.0 to 13.0

Related product manuals