EasyManua.ls Logo

Alstom i4MC - AMBIENT AND MECHANICAL SPECIFICATIONS; Ambient Operating Conditions; Mechanical Dimensions and Material

Alstom i4MC
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i4MC&V/EN M/C User Manual
iSTAT i4MC&V
Page 25
ACCURACY
RMS Current (I
1
) – i4MC 5A 0.5 (0.3**)
62.5V, 125V L-N 0.5 (0.3**)
250V L-N 0.5 (0.3**)
RMS Voltage (U
1
) – i4MV
500V L-N 0.5 (0.3**)
Frequency (actual) 50/60 Hz 0.02Hz
Nominal Frequency Range 16….400 Hz 0.02
THD 5 to 500V 0.5
0.1 to 10A 0.5
0 to 400% 0.5
Total accuracy (measurements and analogue output) according to IEC/EN 60688. Accuracy is defined
as percentage of reading of the measurement except when it is stated as an absolute value.
(** - accuracy on communication)
ANALOGUE OUTPUT
General Linearization Linear, Quadratic
No. of break points 5
Output value limits ± 120% of nominal output
Response time
Input output < 100ms
Residual ripple < 1 % p.p.
DC Current output
Output range values 0…100%
0…1 mA Range 1
0…5 mA Range 2
0...10 mA Range 3
0...20 mA Range 4
Other ranges Programmable using QDSP
Burden voltage 10 V
External resistance RB
max
=10 V / I
outN
DC Voltage output
Output range values 0…100%
0…1 V Range 5
0…10 V Range 6
Other ranges Programmable using QDSP
Burden current 10 mA
External resistance RB
min
= U
outN
/ 10 mA

Table of Contents