User Manual i4MC&V/EN M/C
iSTAT i4MC&V
Page 24
6. TECHNICAL DATA
INPUTS AND SUPPLY
Voltage Input (i4MV) Nominal voltage (Un) 230V
Rating 57.7 ……230V
Overload 277V permanently
2 x Un for 10 seconds
Minimum range 10mV sinusoidal
Burden <0.5 VA
Current Input (i4MC) Nominal current (In) 5A
Rating 1A/5A
Overload (thermal)
(acc. to IEC/EN 60 688)
15A continuously
20 × I
N
; 5 × 1s
Minimal range 2mA sinusoidal
Maximum range 12.5A sinusoidal
Burden <0.3 VA
Frequency Nominal Frequency (Fn) 50/ 60Hz, 400Hz
Measuring range 16 to 400Hz
Power Supply
Universal AC voltage range 40 to 276Vac
Frequency range 45 to 65Hz
DC voltage range 24 to 300Vdc
Burden < 5VA
Power on transient current < 20A 1ms
CONNECTIONS
Permitted conductor cross sections Conductor cross section
Voltage terminals 0.325 … 2.5 mm
2
(22 – 14 AWG) one conductor
Current terminals 0.325 … 2.5 mm
2
(22 – 14 AWG) one conductor
Supply 0.325 … 2.5 mm
2
(22 – 14 AWG) one conductor
I/O Modules and Communications 0.325 … 2.5 mm
2
(22 – 14 AWG) one conductor