i4MC&V/EN M/C User Manual
iSTAT i4MC&V
Page 27
AMBIENT CONDITIONS
Climatic Usage group II
Ambient
Temperature
-10…15…45…55°C Acc. To IEC/EN 60688
Temperature Operation -30 to +70C
Storage -40 to +70C
Humidity 93%RH non condensing
Altitude 2000m
MECHANICAL
Dimensions W45 × H75× D105 mm
Max. conductor cross section for
terminals
2,5 mm
2
with pin terminal
4 mm
2
solid wire
Vibration withstand 7g, 3…100 Hz, 1 oct/min
10 cycles in each of three axes
Shock withstand 300g, 8ms pulse
6 shocks in each of three axes
Mounting Rail mounting 35 × 15 mm
acc. to DIN EN 50 022
Enclosure material PC/ABS
Flammability Acc. to UL 94 V-0
Weight 170 g