EasyManua.ls Logo

Altronix AL1024ULACM - Battery Sizing Calculation Worksheet

Altronix AL1024ULACM
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AL1024ULACM Battery Size Calculation Worksheet:
A. AL1024ULACM internal current consumption (stand-by) ___________________ 0.35 A
B. Load current consumption (stand-by) ___________________ A
C. Stand-by time required (Hours) ___________________ H
D. Battery capacity required for stand-by (A+B)*C ___________________ AH
E. AL1024ULACM internal power consumption (Alarm) ___________________ 0.35 A
F. Load current consumption (Alarm) ___________________ A
G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour) (Alarm) ___________________ H
H. Battery capacity required for Alarm (E+F)*G ___________________ AH
I. Total calculated battery capacity D+H ___________________ AH
J. Battery capacity required I*1.8 (safety factor) ___________________ AH
Note: AL1024ULACM power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in
order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.
ACM series - 9 -
Available from A1 Security Cameras
www.a1securitycameras.com email:sales@a1securitycameras.com