EasyManua.ls Logo

Altronix AL400ULACMCB - Maintenance

Altronix AL400ULACMCB
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
4
- ACMCBseries
4. Connect AC (Fig. 2, pg. 6):
C
onnect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power
c
onnections. Secure green wire lead to earth ground.
K
eep power limited wiring separate from non-power limited
w
iring (115VAC 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.
5. Output options (Fig. 1, pg. 5):
The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation
connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation
connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device
being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
6.
Input trigger options (Fig. 1, pg. 5):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to
the terminal marked [GND].
7.
Fire Alarm Interface options (Figs. 4 through 8, pg. 8):
A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will
trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8].
To disab
le FACP disconnect for an output close the corresponding switch [SW1-SW8].
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).
(b) Normally Closed [NC] input:
For non-latching hook-up (F
ig. 7, pg. 8)
. F
or latching hook-up
(F
ig. 8, pg. 8)
.
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -].
Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition).
Jumper J3 must be cut
(Fig. 4, pg. 8).
8.
FACP Dry form “C” output (Fig. 1A, pg. 5):
Connect desired device to be triggered b
y the unit’
s dry contact output to the ter
minals marked [NO] and [C]
FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
9. Battery Connections
(F
ig. 2, pg. 6)
:
For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of
output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked
[- B
AT +] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
10.
Battery and AC Supervision output (Fig. 2, pg. 6):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory
relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail &
Low/No Battery reporting. Cut “AC delay” jumper to delay report 6 hour.
Note: A tamper s
witch must be installed and connected to the appropriate notification device to report a
troub
le condition w
hen the enclosure door is open.
11.
Multiple power supply inputs (Fig. 1, pg. 5):
When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must
be cut
(Fig. 1B, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8CB to the terminals marked [- Control +] and
connect power for the locking devices to the terminals marked [- Power +]. When using DC power supplies polarity
must be observed. When using AC power supplies polarity need not be observed.
Note: For UL compliance the additional power supply must be power limited, UL Listed for Access Control
Systems and accessories.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level