EasyManua.ls Logo

Amana AIR COMMAND 80 - Page 5

Amana AIR COMMAND 80
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(
ea
While
all
forms
of
building
construction
cannot
be
covered
in
detail,
air
for
combustion,
ventilation
and
dilution
of
flue
gases
for
gas
utilization
equipment
vented
by
natural
draft
normally
may
be
obtained
by
application
of
one
of
the
meth-
ods
covered
in
5.3.3
and
5.3.4.
(f)
Air
requirements
for
the
operation
of
exhaust
fans,
kitchen
ventilation
systems,
clothes
dryers,
and
fireplaces
shall
be
considered
in
determining
the
adequacy
of
a
space
to
pro-
vide
combustion
air
requirements.
5.3.2
Equipment
Located
in
Unconfined
Spaces:
In
uncon-
fined
spaces
in
buildings
infiltration
may
be
adequate
to
pro-
vide
air
for
combustion,
ventilation,
and
dilution
of
flue
gases.
However,
in
buildings
of
unusually
tight
construction
addi-
tional
air
shall
be
provided
using
the
methods
described
in
5.3.3-b
or
5.3.4.
Space,
Unconfined.
For
purposes
of
this
Code,
a
space
whose
volume
is
not
less
than
50
cubic
feet
per
1,000
Btu
per
hour
of
the
aggregate
input
rating
of
all
appliances
installed
in
that
space.
Rooms
communicating
directly
with
the
space
in
which
the
appliances
are
installed,
through
openings
not
furnished
with
doors,
are
considered
a
part
of
the
uncon-
fined
space.
5.3.3
Equipment
Located
in
Confined
Spaces:
(a)
All
Air
from
Inside
the
Building:
The
confined
space
shall
be
provided
with
two
permanent
openings
communicating
directly
with
an
additional
room(s)
of
sufficient
volume
so
that
the
combined
volume
of
all
spaces
meets
the
criteria
for
an
unconfined
space.
The
total
input
of
all
gas
utilization
equip-
ment
installed
in
the
combined
space
shall
be
considered
in
making
this
determination.
Each
opening
shall
have
a
mini-
mum
free
area
of
1
square
inch
per
1,000
Btu
per
hour
of
the
total
input
rating
of
all
gas
utilization
equipment
in
the
con-
fined
space,
but
not
less
than
100
square
inches.
One
open-
ing
shall
be
within
12
inches
of
the
top
and
one
within
12
inches
of
the
bottom
of
the
enclosure.
(See
Figure
1.)
CHIMNEY
or
GAS
VENT
OPENINGS
Note:
Each
opening
shall
have
a
free
area
of
not
less
than
one
square
inch
per
1,000
Btu
per
hour
of
the
total
input
rat-
ing
of
all
equipment
in
the
enclosure,
but
not
less
than
100
square
inches.
Fig.
1.
Equipment
Located
in
Confined
Spaces;
All
Air
from
inside
the
Build-
ing.
See
5.3.3-a.
(b)
All
Air
From
Outdoors:
The
confined
space
shall
be
pro-
vided
with
two
permanent
openings,
one
commencing
within
12
inches
of
the
top
and
one
commencing
within
12
inches
of
the
bottom
of
the
enclosure.
The
openings
shall
communi-
cate
directly,
or
by
ducts,
with
the
outdoors
or
spaces
(crawl
or
attic)
that
freely
communicate
with
the
outdoors.
y
,
1.
When
directly
communicating
with
the
outdoors,
each
opening
shall
have
a
minimum
free
area
of
1
square
inch
per
4,000
Btu
per
hour
of
total
input
rating
of
all
equip-
ment
in
the
enclosure.
(See
Figure
2.)
CHIMNEY
or
GAS
VENT
VENTILATION
LOUVERS
(each
end
of
attic)
ALTERNATE
AIR
INLET
VENTILATION
LOUVERS
FOR
UNHEATED
CRAWL
SPACE
Note:
The
inlet
and
out-
let
air
openings
shall
each
have
a
free
area
of
not
less
than
one
square
inch
per
4,000
Btu
per
hour
of
the
total
input
rat-
ing
of
all
equipment
in
the
enclosure.
Fig.
2.
Equipment
Located
in
Confined
Spaces;
All
Air
from
Outdoors
Inlet
Air
from
Ventilated
Crawl
Space
and
Outlet
Air
to
Ventilated
Attic.
See
5.3.3-b.
2.
When
communicating
with
the
outdoors
through
vertical
ducts,
each
opening
shall
have
a
minimum
free
area
of
1
square
inch
per
4,000
Btu
per
hour of
total
input
rating
of
all
equipment
in
the
enclosure.
(See
Figure
3.)
CHIMNEY
or
GAS
VENT
VENTILATION
LOUVERS
leach
end
of
attic)
Note:
The
inlet
and
out-
let
air
openings
shall
each
have
a
free
area
of
not
less
than
one
square
inch
per
4,000
Btu
per
hour
of
the
total
input
rat-
ing
of
all
equipment
in
the
enclosure.
INLET
AIR
DUCT
(ends
1
ft.
above
floor)
Fig.
3.
Equipment
Located
in
Confined
Spaces;
All
Air
from
Outdoors
Through
ventilated
Attic.
See
5.3.3-b.
3.
When
communicating
with
the
outdoors
through
horizon-
tal
ducts,
each
opening
shall
have
a
minimum
free
area
of
1
square
inch
per
2,000
Btu
per
hour
of
total
input
rating
of
all
equipment
in
the
enclosure.
(See
Figure
4.)
4.
When
ducts
are
used,
they
shall
be
of
the
same
crosssec-
tional
area
as
the
free
area
of
the
openings
to
which
they
connect.
The
minimum
dimension
of
rectangular
air
ducts
shall
be
not
less
than
3
inches.
5

Related product manuals