34
2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680
3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920
•
5. Use the HVAC phone application to
congure/test operations.
a. Two-stage outdoor units:
a.Provide a second stage cooling call from the
thermostat and charge accordingly.
b. Single-stage outdoor units:
a.Provide a cooling call from the thermostat and
charge accordingly.
a. Two stage operation using the
HVAC application:
a. Select the gas heat icon after entering the
furnace menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for
high stage operation.
3. Select the Non-Comm Outdoor Setting menu (OdS)
using the on board push buttons or the
HVAC phone application. Select 1 AC for single stage
Air Conditioners, 1HP for single stage heat pumps,
2 AC for two stage air conditioners and 2 HP for two
stage Heat Pumps.
4. Go to the tonnage units menu (ton) and select the
tonnage value that corresponds to the desired airow
for the outdoor unit. See the following table.