4
Figure 1 Correct installation of flexible gas connection
*NOTE*
H
OT POSITION
50 ± 20 mm
± 5mm
Union
end
Valve
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 11984 Class 1 Type C Construction
1
Metre Long - Ambi~Rad Part No. 6500-2
*NOTE* - CORRECT INSTALLATION AS SHOWNWILLALLOW
FOR APPROX. 150 mm OF MOVEMENT DUETO EXPANSION.
T
HIS INSTALLATION LAYOUT ISTHE ONLY METHOD RECOMMENDED
B
Y THE INSTITUTE OF GAS ENGINEERS,THE MANUFACTURER AND
A
MBI-RAD LTD
N.B. BURNER ILLUSTRATED ISAR SERIES, BUT INSTRUCTIONS
ARE EQUALLY APPLICABLE TO ALL OTHER RANGES OF BURNERS.
NOTE:THESE INSTRUCTIONS MUST BE CARRIED OUT IN
A
CCORDANCEWITH THE RELEVANT PROVISIONS OFTHE
G
AS SAFETY (INSTALLATIONS AND USE) REGULATIONS 1984
(
AS AMENDED) ANDTHE MANUFACTURERS RECOMMENDATIONS
.
NOTE:
Elbows must be fitted to eliminate
sharp bends near end fittings.
4
00
±
7
5
m
m
V
alve
COLD POSITION
*NOTE*
HOT POSITION
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 11984 Class 1 Type C Construction
6
00 mm Long - Ambi~Rad Part No. 6500
*N
OTE* - CORRECT INSTALLATION AS SHOWNWILL ALLOW
F
OR APPROX. 100 mm OF MOVEMENT DUETO EXPANSION.
T
HIS INSTALLATION LAYOUT ISTHE ONLY METHOD RECOMMENDED
BY THE INSTITUTE OF GAS ENGINEERS,THE MANUFACTURER AND
A
MBI-RAD LTD
N
.B. BURNER ILLUSTRATED ISAR SERIES, BUT INSTRUCTIONS
A
RE EQUALLY APPLICABLE TO ALL OTHER RANGES OF BURNERS.
N
OTE:THESE INSTRUCTIONS MUST BE CARRIED OUT IN
A
CCORDANCEWITH THE RELEVANT PROVISIONS OFTHE
G
AS SAFETY (INSTALLATIONS AND USE) REGULATIONS 1984
(AS AMENDED) ANDTHE MANUFACTURERS RECOMMENDATIONS
.
N
OTE:
Elbows must be fitted to eliminate
sharp bends near end fittings.
Valve
2
3
0
±
7
5
mm
50 ± 20 mm
C
OLD
P
OSITION
± 5mm
Union
end
Valve
XX
XX
XX
COLD POSITION
COLD
POSITION
COLD
POSITION
XX
Greater than 5 mm