20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
SMD17E2 User Manual
INSTALLING THE SMD17E2
91
1.6 Input Wiring
Inputs 1 and 2 are single ended inputs that share the DC Common return pin. They accept 3.5 to 27 Vdc with-
out the need for an external current limiting resistor. Figure T1.5 below shows how to wire discrete DC sourc-
ing and sinking sensors to inputs 1 and 2 of the SMD17E2. Colors in parentheses are the appropriate wire
color of the CNPL-5M cable.
Figure T1.5 Input Wiring
1.6.1 Cable Shields
Because they are low power signals, cabling from the sensor to the
SMD17E2 should be done using a twisted pair cable with an overall
shield. The shield should be grounded at the end when the signal is gen
-
erated, which is the sensor end. If this is not practical, the shield should
be grounded to the same ground bus as the SMD17E2.
1.6.2 Sinking Sensors Require a Pull Up Resistor
Sinking output sensors require an external pull up resistor because
inputs 1 and 2 of the SMD17E2 units also sink current. Table T1.1
below shows the values of pull up resistors that will allow the unit’s
input to activate along with the current that the sensor must be able to
sink when it is active.
Table T1.1 TIA/EIA Color Codes
The logical states of the sensor and SMD17E2 input will be reversed. The SMD17E2 input is off when the
sensor is active. You can set the logic state of the input when you configure the unit.
Input
Voltage
Pull Up
Resistor
Sensor Current
When Active
5 Vdc 300 ohm 16.7 mA
12 Vdc 1.4 kilohm 8.6 mA
24 Vdc 3.8 kilohm 6.3 mA
Input1 or Input2
Input1 or Input2
DC Common
DC Common
+
+
+
+
–
(WHT or BLK)
(WHT or BLK)
–
5 to
24 Vdc
5 to
24 Vdc
PNP
Sourcing
Sensor
NPN
Sinking
Sensor
Out
Out
R
PULLUP
See 1.7.1
See 1.7.1
See 1.7.2
Input
Optocoupler
Optocoupler
DC Common
Figure T1.6 Input Schematic