77
Technical Data
OMMG00012 Rev 12 – NOV 2019
9.1.5 Valve Sizing Calculations
Pressure Drop
The G valve is designed to produce minimal pressure drop. The normal
recommendation when determining the size of an AMOT G valve is a pressure
drop between 0.01 and 0.1 bar (0.145 and 1.45 psi).
Valve Flowrate
A Kv is the valve’s flow coefficient. It is defined as the number of cubic metres
of room temperature water that flows through the valve with a pressure drop
of 0.069 bar (Cv is the imperial coefficient). See the table below for examples
of Kv and Cv for the G valves:
Note
Cvs are applicable to 90° rotor versions only. For 180°
versions:
The basic formula to determine the
Kv of a valve is:
The basic formula to determine the
Cv of a valve is:
= Flow (m
3
/h)
= Pressure drop (bar)
= Specific gravity of
fluid
= Specific gravity
of fluid
The formulae for finding flow (m
3
/h) or
pressure drop (bar) are shown below:
The formulae for finding flow (US
gallons/min) or pressure drop (psi)
are shown below: