49
PROBLEM
SOLUTION
PROBABLE REASON
The machine does not
reach the set temperature.
The cooling system is not work-
ing correctly (continual request
for “hot”, the temperature does not
rise).
The temperature adjustment sys-
tem does not carry out the requests
for hot or cold correctly.
The internal fan is not working.
Some other reason not mentioned
above.
Check the maximum and minimum set temperature
values on the hardware thermostat. If this does not
resolve the problem, contact your technical assistance
service.
Contact your technical assistance service.
Contact your technical assistance service.
Contact your technical assistance service.
The machine does not
reach the set humidity.
Error in setting of setpoint.
The wet bulb gauze is dirty or badly
positioned.
The wet bulb gauze is dry because
there is no water in the supply pipe.
Error in temperature control. In this
condition there is also an error in
humydity control.
The test material prevents air from
circulating correctly.
The test material dissipates too
much heat.
The door is not shut correctly.
Continual request for “humid, (the
dehumidification system is not
working correctly).
Continual request for “dry”, (the
dehumidification system is not
working correctly).
The humidity adjustment system
does not carry out the requests for
humid or dry correctly.
Check and modify.
Check and reposition correctly or replace.
Contact your technical assistance service
Follow the “solutions” given for “the machine does not
reach the set temperature value”.
Place the material so that air can circulate through the
intake and outlet openings.
Check and reduce the load that dissipates the heat
according to the technical specifications of the cham-
ber.
Close the door correctly.
Contact your technical assistance service.
Contact your technical assistance service.
Contact your technical assistance service
The machine is noisy.
The chamber is not resting correctly
on the floor.
Contact with foreign bodies.
Fault in the mechanical parts.
The chamber has been placed on a
site with a lot of reverberations.
Check.
Check that foreign bodies, such as cartons or other
structures are not touching the equipment thus causing
vibrations during operations.
Check that moving mechanical parts e.g. fans are not
making a noise.
Contact your technical assistance service.
The light does not switch
on.
Lamp burnt out.
Faulty switch.
Replace the lamp.
Contact your technical assistance service.

Table of Contents