16
the PID and software
algorithm for the given
output (1/2/3)
10: SpSt
start/stop of outputs 1/2/3
with function 9: cLEA,
messages Star/StoP/ cLEA
when power is on, default stop
11: StSP
default start (only for [F] and [SET])
67: HSEt control signal
setpoint (MV) for outputs
in manual mode
0 ÷ 100 %
applies to all outputs (1, 2, 3 and analog one), 100 % means the
maximum available output power (set with parameters 13/20/27:
oPF1/2/3 ), step by 1% (4)
50.0 %
68: bSEt Lock of quick
setpoint changes
SEt1/2/3 , (chapter 9.1)
0: oFF = no locks, 1/2/3: SEt1/2/3 = lock of one of the settings (SEt1/2/3 ),
4: SE12 = simultaneous for SEt1 and SEt2 , 5: SE13 = for SEt1 and SEt3 ,
6: SE23 = for SEt2 and SEt3 , 7: ALL = for all settings ( SEt1 , SEt2 and SEt3 )
oFF
69: PPro protection of
configuration with an
access password
0: oFF = entering the manual and remote configuration menu is not
protected with a password, 1: on = manual and remote configuration (only for
ARSOFT-CFG) is protected with password
on
70: PASS access password 0000 ÷ 9999
password for entering the configuration menu and for the
MQTT (chapter 11.1)
1111
VII. DISPLAY OPTIONS, submenu diSP
71: briG brightness 10 ÷ 100 %
display brightness, step by 10%
100
%
72: wnit display unit of
measurement
0: nonE = none, 1: M =m, 2: ma = mA, 3: A = A, 4: mW = mV, 5: W = V, 6:
o
C =°C, 7:
PrH = %RH, 8: PErc =%, only for AR632.B/652.B/682.B: 9: k = k, 10: Pa = Pa, 11:
kPa = kPa
o
C
73: dibo displayed value
for the bottom line
0: oFF = none, 1/2/3: con1/2/3 =setpoint for output 1/2/3, 4/5/6: bar1/2/3 =
MV1/2/3 bargraph ( output 1/2/3 MV control signal in the range 0÷100%), 7:
barA = bargraph for mA/V output, 8: barP = PV bargraph (measurement in the
range : irLo ÷ 5: irHi )
con1
VIII. COMMUNICATION OPTIONS FOR RS485 AND ETHERNET, submenu trAn , description in chapters 11 ÷ 11.5
74: r4br speed for RS485 bitrate kbit/s, 0: 2.4 , 1: 4.8, 2: 9.6, 3: 19.2, 4: 38.4, 5: 57.6, 6: 115.2
19.2 kbit /
s
75: r4cF RS485 character
format
selection of parity and stop bits, 0: 8N1 (none), 1: 8E1 (even), 2: 8o1 (odd),
3: 8N2
8N1
76: Addr MODBUS-RTU
address
1 ÷ 247
device address for RS485 and suffix (suffix) for the name, (5)
1
77: EtMo Ethernet interface
operating mode (MAC
hardware address available
from ARSOFT-CFG and
MODBUS-RTU/TCP)
0: oFF
Ethernet always off (recommended when not in use)
oFF
1: Auto
DHCP client enabled, network parameters (from 78: EIP3 to 89:
EGA0, i.e. device IP address, mask and gateway) are set automatically
2: StAt
DHCP client disabled, network parameters are set manually
78÷81: EIP3/2/1/0 IP
address
0 ÷ 255
device's IPv4 address in the local network (Ethernet), 4
consecutive octets
192.168.0.200
82÷85: ESu3/2/1/0 IP mask
0 ÷ 255
mask of the IPv4 address in the local network (Ethernet), 4
consecutive octets
255.255.255.0
86÷89: EGA3/2/1/0 IP
gateway
0 ÷ 255
router's IPv4 address in the local network (Ethernet), 4
consecutive octets
192.168.0.1
90: EtcP MODBUS-TCP
port
1÷999
9
TCP port number for the MODBUS-TCP protocol (also for ARSOFT-
CFG)
502
91: MqMo operating mode
and type of published
MQTT messages (Ethernet)
(detailed description of
MQTT communication,
chapter 11.1)
0: oFF
MQTT protocol disabled (recommended when not used)
oFF
1: PW
MQTT protocol enabled, only measurement (PV) in the publication,
e.g. "4.5"
2: PWun
MQTT protocol enabled, measurement (PV) and unit in the
publication
3: nAPW
MQTT enabled, device name, PV and unit in text, (5)