6 Smart-UPS VT Battery Breaker Box, 10-40kVA, 400V, Installation and Operation 990-12411
Site Planning
Environmental considerations
Placing
Place the Battery Breaker Box as close to the battery bank as possible and make sure that access to
the Battery Breaker Box is easy.
Temperature
Range:
0° to 40°C
Keep Ventilated
Front-to-Rear
Airflow
(see space
considerations)
Relative
Humidity: <95%
Non-condensing
No Conductive
Dust or
Corrosive
Fumes
Altitude derating table:
1000m: 100% load
1500m: 95% load
2000m: 91% load
2500m: 86% load
3000m: 82% load