2021/07/12 Rev4.4 Quick Installation Guide
1
QS1 Microinverter Quick Installation Guide
The sketch of QS1 support system.
All the PV modules are placed into two lines. Then put a QS1 in the middle of the two lines and make sure it is easy to
connect with four PV modules which are next to it, as well all the cables.
Step 1. Verify the grid voltage to match with microinverter rating
Step 2. The AC bus distribution
a. The AC bus is arranged at the proper position of the microinverter.
b. One end of the AC bus access junction box into power grid.
c. Wire the conductors of the AC bus: L1 - BLACK; L2 - RED;PE - GREEN.
NOTE: Wiring colour code can be different according local regulation, check all the wires of the installation before
connecting to the AC bus to be sure they match.Wrong cabling can damage irreparably the microinverters, such an issue is
not covered by the warranty.
Step 3. Attach the APsystems Microinverters to the racking
NOTE: Do not place the microinverters (including DC and AC connectors) where exposed to the sun, rain or snow, even gap
between modules. Allow a minimum of 3/4’’(1.5cm) between the roof and the bottom of the microinverter to allow proper air
flow.The racking of install microinverter must be reliably grounding.
a. Mark the location of the microinverter on the rack, with respect to the PV module junction box or any other
obstructions.
b. Mount one microinverter at each of these locations using hardware recommended by your module racking
vendor.when install microinverter, grounding washer Must be facing the racking.
Step 4. Ground the system
a. There already has earth wire inside the AC cable, thus the grounding work could be done directly by it.
b. For those areas that have special requirements, the external grounding work could be done by grounding brackets.
Step 5. Connect the APsystems Microinverter to AC bus cable
Push the microinverter AC connector to the Bus cable connector. Listen for the "Click".
Please scan the QR code to get
mobile app and more support
to help the installation.
Power grid
grounding washer
Warning injure hand
grounding brackets
NOTE:Forbidden to hand carry the
inverter through AC cable.

Other manuals for APsystems QS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APsystems QS1 and is the answer not in the manual?

APsystems QS1 Specifications

General IconGeneral
ModelQS1
ManufacturerAPsystems
TypeMicroinverter
Max Output Power1200VA
Number of MPPTs4
Efficiency96.5%
Startup Voltage22 V
Maximum Input Current12 A
Nominal Output Frequency60 Hz
Power Factor>0.99
Total Harmonic Distortion (THD)<3%
Enclosure RatingIP67
Operating Temperature Range-40°C to +65°C
CoolingNatural Convection
Protection LevelIP67
CommunicationZigbee
Output Voltage Range211 V - 264 V