Flex 8ES/EX Standard, AB and Tandem Instruction Manual (CE)
November 2016
Page 29 of 45
4.2.4 Jumper Settings
Jumper setting applies to functions such as the standard or
reversed logic A/B selector sequence, transmitter inline
pushbutton configurations, firmware version, system testing
and remote pairing methods.
Jumper Settings Function
JP2
(Inserted)
START command is required when receiver MAIN relays
are deactivated (cancels ANY button setting on section 4.1.4).
JP3
(Opened)
Standard A/B selector sequence - Output
relay A activated at A position, output relay B activated at B position,
both relays activated at A+B position.
JP3
(Inserted)
Reversed logic A/B selector sequence - Output
relay B activated at A position, output relay A activated at B position,
both relays deactivated at A+B position.
JP4
(Opened)
JP5
(Opened)
Standard right/left pushbutton configuration
JP4
(Inserted)
JP5
(Opened)
Inline top/bottom pushbutton configuration for PB1 to PB8
JP4
(Opened)
JP5
(Inserted)
Inline top/bottom pushbutton configuration for PB1 to PB12
JP4
(Inserted)
JP5
(Inserted)
Inline top/bottom pushbutton configuration for PB1 to PB4
JP6
(Inserted)
System firmware version
JP7
(Inserted)
For system testing only (receiver MAIN relays disabled)
JP8
(Opened)
Receiver-to-transmitter remote pairing
(pressing the Pairing button required)
JP8
(Inserted)
Receiver-to-transmitter remote pairing
(pressing the Pairing button not required)