P12x/EN IN/A96 Handling, Installation and Case Dimensions
Page 8/10 MiCOM P120/P121/P122/P123
6. DIMENSIONS
6.1 Connection of power terminals, and Signals terminals
The individual equipment are delivered with sufficient M4 screws to connect the relay via
annular terminals, with a maximum recommended of two annular terminals per contact.
If necessary, AREVA T&D can provide annular terminals to crimp. 5 references exist
according to the section of the wire (see below). Each reference corresponds to a sachet of
100 terminals.
Push-on connector 4.8 x 0.8 (wire size 0.75 - 1.5mm²)
AREVA T&D'S Automation & Information Systems Business
reference: ZB9128 015
Push-on connector 4.8 x 0.8mm (wire size 1.5 - 2.5mm²)
AREVA T&D'S Automation & Information Systems Business
reference: ZB9128 016
P0166ENb
M4 90˚ Ring Tongue terminal (wire size 0.25 - 1.65mm²)
AREVA T&D'S Automation & Information Systems Business reference,
Stafford part number ZB9124 901
M4 90˚ Ring Tongue terminal (wire size 1.5 - 2.5mm²)
AREVA T&D'S Automation & Information Systems Business reference,
Stafford part number ZB9124 900
P0167ENb