Technical Guide P92x/EN FT/E11
User Guide
MiCOM P921-P922-P923 Page 49/110
[81] F3=
50.0 Hz
Description : setting of the 3
rd
stage
Range : from "fn – 10Hz" to "fn + 10Hz"
[81] tF3=
0 ms
Description : time delay setting
Range : from 0 to 599s, step = 0.01s
[81] F4=
NO
Description : configuration of the 4
th
stage
Range : NO / 81> / 81<
[81] F4=
50.0 Hz
Description : setting of the 4
th
stage
Range : from "fn – 10Hz" to "fn + 10Hz"
[81] tF4=
0 ms
Description : time delay setting
Range : from 0 to 599s, step = 0.01s
[81] F5=
NO
Description : configuration of the 5
th
stage
Range : NO / 81> / 81<
[81] F5=
50.0 Hz
Description : setting of the 5
th
stage
Range : from "fn – 10Hz" to "fn + 10Hz"
[81] tF5=
0 ms
Description : time delay setting
Range : from 0 to 599s, step = 0.01s
[81] F6=
NO
Description : configuration of the 6
th
stage
Range : NO / 81> / 81<
[81] F6=
50.0 Hz
Description : setting of the 6
th
stage
Range : from "fn – 10Hz" to "fn + 10Hz"
[81] tF6=
0 ms
Description : time delay setting
Range : from 0 to 599s, step = 0.01s