Technical Guide P92x/EN CT/E11
Modbus Protocol
MiCOM P921-P922-P923 Page 31/118
1.7.5.2 Overvoltage protection (P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
0330 V> configuration 0-2 1 - F55 0
0331 Threshold V> 50 to 2000
or
200 to 7200
1
or
5
V/10 F1 1300
or
4800
0332 Type of temporisation 0 to 1 1 - F27 0
0333 TMS value V> 5 to 1000 5 1/10 F1 10
0334 tRESET temporisation 0 to 10000 1 1/100 s F1 1
0335 V> temporisation 0 to 59999 1 1/100 s F1 4
0336 to
033F
Reserved 0
0340 V>> configuration 0-2 1 - F55 0
0341 Threshold V>> 50 to 2600
or
200 to 9600
1
or
5
V/10 F1 1300
or
4800
0342 V>> temporisation 0 to 59999 1 1/100 s F1 1
0343 to
034F
Reserved 0
0350 V>>> configuration 0-2 1 - F55 0
0351 Threshold V>>> 50 to 2600
or
200 to 9600
1
or
5
V/10 F1 1300
or
4800
0352 V>>> temporisation 0 to 59999 1 1/100 s F1 1
0353 to
035E
Reserved 0
035F V> Hysteresis 95 to 98 1 % or
1/100
F1 98
1.7.5.3 Zero sequence overvoltage protection (P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
0360 Vo> configuration 0-1 1 - F24 0
0361 Threshold Vo> 5 to 1300
or
20 to 4800
1
or
5
V/10 F1 50
or
200
0362 Type of temporisation 0 to 1 1 - F27 0
0363 TMS value Vo> 5 to 1000 5 1/10 F1 10
0364 tRESET temporisation 0 to 10000 1 1/100 s F1 1
0365 Vo> temporisation 0 to 59999 1 1/100 s F1 4
0366 to
036F
Reserved 0
0370 Vo>> configuration 0-1 1 - F24 0
0371 Threshold Vo>> 5 to 1300
or
20 to 4800
1
or
5
V/10 F1 50
or
200
0372 Vo>> temporisation 0 to 59999 1 1/100 s F1 4
0373 to
037F
Reserved 0
0380 Vo>>> configuration 0-1 1 - F24 0