P92x/EN CT/E11 Technical Guide
Modbus Protocol
Page 34/118 MiCOM P921-P922-P923
1.7.5.6 Under/overfrequency protection (P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
03D0 f1 0-2 1 - F56 0
03D1 Threshold f1 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03D2 f1 temporisation 0 to 59999 1 1/100 s F1 4
03D3 f2 0-2 1 - F56 0
03D4 Threshold f2 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03D5 f2 temporisation 0 to 59999 1 1/100 s F1 4
03D6 f3 0-2 1 - F56 0
03D7 Threshold f3 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03D8 f3 temporisation 0 to 59999 1 1/100 s F1 4
03D9 f4 0-2 1 - F56 0
03DA Threshold f4 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03DB f4 temporisation 0 to 59999 1 1/100 s F1 4
03DC f5 0-2 1 - F56 0
03DD Threshold f5 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03DE f5 temporisation 0 to 59999 1 1/100 s F1 4
03DF f6 0-2 1 - F56 0
03E0 Threshold f6 4000 to 6000
if fn= 50Hz
5000 to 7000
if fn= 60Hz
1 1/100 Hz F1 5000 or
6000
03E1 f6 temporisation 0 to 59999 1 1/100 s F1 4