WARNING: The feeder breaker must be in the “off” position before at-
tempting to install the Module AC Connections on the rear of the cabi-
net shelf. :WARNING
4.4.2 A.C. Connections
Confirm the operating voltage before proceeding.
WARNING: Ensure that the input and output breakers are in the “off”
position prior to any work being performed on the A.C. or D.C. con
-
nections. :WARNING
Remove the rear cover via the two captive slotted fasteners. Note the connection legend affixed to
the bus bar insulating cover. Input wires can be routed through the access holes located on either
side of the shelf.
Refer to the connection drawing in Figure #6 or Figure #7 to determine the location of the AC in
-
put connections.
Standard AC cable knock outs for the 3 Module and 4 Module RSM 48/30 & 24/50 shelves are:
Left Side - 1" conduit
Right Side - no provision for AC cable
Standard AC cable knock outs for the 3 Module RSM 48/50 & 24/100 shelves are:
Left Side - no standard conduit size (must order appropriate accessory)
Right Side - Blank Plate
Standard AC cable knock outs for the 4 Module RSM 48/50 & 24/100 shelves are:
Left Side - 1-1/2" knock out
Right Side - Blank Plate
ARGUS TECHNOLOGIES 010-030-C0 Rev E Page 17 of 42