6.0 Status mode - Local
Any alarm messages are detailed on the menu tree and under the individual alarm description. The
operator also has the ability to retrieve operating data via the menu and the front panel display as
well as by remote connection. These “status” parameters include:
1) Module ID #
2) Module Settings ......-Float Voltage
....................-Equalize Voltage
....................-Slope %
....................-Current Limit
....................-Start Delay
....................-High Voltage Shutdown Point
....................-LowVoltage Alarm
....................-High Voltage Alarm
....................-Backlight Time Out
....................-Equalize Time Out
....................-Return
....................-Exit
3) Input AC Voltage RMS (+/- 5% nominal)
4) Fan Speed
5) Fan Setting
6) Internal Ambient Temperature
7) Heat Sink Temperature
8) Forced Share Enable/Disable Master/Slave
9) Remote Communication Access/Lockout
10) Current Limit Alarm Enable/Disable
11) Software Version #
The internal ambient temperature reading is the internal ambient temperature of the module. If the
fan fails to operate for some reason, the internal ambient temperature will approach the heat sink
temperature. If the AC input breaker in the module is open and there is DC power at the output ter-
minals (output DC breaker closed), then the heatsink temperature will be unavailable and will read
N/A. The internal ambient temperature will still read correctly.
ARGUS TECHNOLOGIES 010-030-C0 Rev E Page 29 of 42