7.0 Adjustments
7.1 Factory Settings / Ranges
7.1.1 48 volt units
Function
Range/ modes Factory setting
Float Voltage 48-57VDC 52.25VDC
Equalize Voltage 50-60VDC 54.25VDC
Test Voltage 42-62VDC N/A
HIgh Voltage Shutdown Point 54-61VDC 56.0VDC
Low Voltage Alarm 42-48VDC 44.0VDC
High Voltage Alarm 44-60VDC 55.4VDC
Current Limit (30A unit) 9-33 Amps 31.0 Amps
Current Limit (50A unit) 15-55 Amps 51.0 Amps
Output Slope (30A unit) 0-2% 0.09%
Output Slope (50A unit) 0-2% 0.1%
7.1.2 24 volt units
Function
Range Factory setting
Float Voltage 24-28.5VDC 26.1VDC
Equalize Voltage 25-30.5VDC 27.1VDC
Test Voltage 21-31VDC 24.0VDC
High Voltage Shutdown Point 27-30VDC 28.0VDC
Low Voltage Alarm 21-24VDC 22.0VDC
High Voltage Alarm 22-30VDC 27.7VDC
Current Limit (50A unit) 15-55 Amps 51 Amps
Current Limit (100A unit) 30-110 Amps 102 Amps
Output Slope (50A unit) 0-2% 0.09%
Output Slope (100A unit) 0-2% 0.1%
7.1.3 Common to 24 volt and 48 volt units
Forced Sharing enabled/disabled
disabled
Delay Start 0-500 sec 0 seconds
Back light time-out 0-60 minutes 5 minutes
Equalize time-out 1-30 hours 30 hr.
Current limit alarm enable/disable disable
Remote Access access/lockout lockout
Remote Adjust access/lockout lockout
Module ID# 01-99 01
Local access alarm enable/disable enable
Security code 000-999 123
WARNING: No adjustments should be made to the module while the
input breaker is open or the AC Mains voltage is outside the range
stated in the specifications. Final adjustments should be done only
when the unit has reached operating temperature. Warm-up of 15 min
-
utes is sufficient. :WARNING