MANUAL ADDENDUM
MANUAL ADDENDUM
FORM 954-010-10 - Add2.doc 2/5/98
P.2
Function 24 volt systems (nom) 48 volt systems (nom)
Float
27 54
TABLE 1-3: RSM 48/7.5 and 24/15 SUPERVISORY/CONTROL MODULE
Function 24 volt systems (nom) 48 volt systems (nom)
LVD
21 42
TABLE 1-4: SUPERVISORY/CONTROL SYSTEMS (SD-02,03,04,05)
Function 12 volt systems (nom) 24 volt systems (nom) 48 volt systems (nom)
Load Out
10.5 21 42
Load In
12.5 25 50
LVA
12 24 48
HVA
14 28 55.5
HVSD
n/a 29.5 58
NOTE: THIS ADDENDUM SHEET IS TO BE INSERTED IN ALL OF THE ABOVE LISTED