5.9 EXHAUSTIC CONTROL (CF open chamber)
Supplying the card, the control system of proper combusted smoke exhaust is carried out by means of an
automatic reset thermostat. “Fume protection” enabling stops the boiler on safety and it will be displayed on
the control panel with the relevant error code 6 01
This intervention can be caused by:
A thermostat temperature raise, the fume enabling threshold is 75±3°C.
After 12 minutes after restoring the fumes thermostat the protection will be automatically disabled.
Timing can be zeroed by the ON/OFF electric supply of the card.
Automatic
thermostat
reset