7.2.3 Menù 4 : Zone 1 parameters
2
5
2
Sanitary delay start
(anti water hammering) (dec)
5 ÷ 200
5
2
5
3
Sanitary switch off logic
0: anti-scale (62 o 65°C).
1: set-point+4°C
0
2
5
4
Sanitary post-circulation and
post-ventilation
0: Post-ventilation: Tflow<75°C = no post-
ventilation; Tflow>75°C = 3 min (minimum
speed); Post-circulation: 30sec
1: Post-ventilation: 3min
Post-circulation: 3min
0
2
5
5
Heating start delay after sanitary
(min)
0 ÷ 30
0
2
5
7
Antilegionella function (only for
boilers with external thank and
NTC sensor par. 228 = 1)
0: disabled
1: enabled
0
2
5
8
Antilegionella frequency (h)
24 ÷ 720
100
2
5
9
Antilegionella temperature (°C)
60 ÷ 70
66
2
6
BOILER MANUAL SETTING
2
6
0
Manual mode attivation
0: Off
1: On
0
2
6
1
Boiler pump control
(set parameter 260 =1)
0: Off
1: On (timed 10 min)
0
2
6
2
Fan control
(set parameter 260 =1)
0: Off
1: On (timed 10 min)
0
2
6
3
Diverter valve control
(set parameter 260 =1)
0: Sanitary
1: Heating ( timed 10 min)
0
2
7
TEST & UTILITIES
2
7
0
Flue cleaning function
0: Off
1: On (select desired power)
0
2
7
1
Air Purge function
0: Off
1: On
0
2
8
RESET MENU’
2
8
0
Reset menu 2 factory setting
YES: press button “OK”
NO: press button “ESC”
/
Menù
Sub Menù
Parameter
Function
Range
Default
setting
4
0
SETPOINT
4
0
2
Temperature setpoint zone 1
Par 425 ÷ Par 426
/
4
2
ZONE 1 SETTING
4
2
0
Select high or low temperature
for zone 1
(only with zone module)
0: low temperature
1: high temperature
1
4
2
1
Thermoregulation mode
selection
0: fixed delivery temperature
1: basic thermoregulation
2: only room probe
3: only outside probe
4: room probe + external probe
1
4
2
2
Select thermoregulation curve
0_2 ÷ 1_0 (par. 420=0)
1_0 ÷ 3_5 (par. 420=1)
(with Auto function enabled)
0_6 (par 420=0)
1_5 (par 420=1)
4
2
3
Select thermoregulation curve
parallel shifting
-7 ÷ 7 (par. 420=0)
-14 ÷ 14 (par. 420=1)
(with Auto function enabled )
0