1X-F Series Operation Manual 23
Testing fire routing (or warning for NBN S 21-100)
Note: Always notify the fire brigade of any planned fire routing tests.
To test fire routing (or warning for NBN S 21-100), press the General Test button,
and then press the Fire Routing ON/ACK button (or Warning Start/Stop button for
NBN S 21-100).
The test is indicated as follows:
General Test LED: On steady.
Fire Routing On/Ack LED (or Warning Start/Stop LED for NBN S 21-100): On
steady yellow.
Fire Routing On/Ack LED: Flashing red.
Sounders: Test signal (3 seconds on, 5 seconds off)
To end the test, press the General Test button, and then press the Fire Routing
On/Ack button (or Warning Start/Stop button for NBN S 21-100) again.
If there is a fire alarm the fire panel will exit the test and respond to the alarm as
configured.
Disabling or enabling fire routing (or warning for NBN S 21-100)
To disable fire routing (or warning for NBN S 21-100), press the General Disable
button, and then press the Fire Routing On/Ack button (or Warning Start/Stop
button for NBN S 21-100).
Disabled fire routing (or warning for NBN S 21-100) is indicated as follows:
General Disable LED: On steady.
Fire Routing On/Ack LED (or Warning Start/Stop LED for NBN S 21-100): On
steady yellow.
To enable fire routing (or warning for NBN S 21-100), press the General Disable
button, and then press the Fire Routing ON/ACK button (or Warning Start/Stop
button for NBN S 21-100) again.
Note: Disabled fire routing (or warning for NBN S 21-100) does not operate or
indicate a fault if there is a fire alarm.