24 1X-F Series Operation Manual
Disabling or enabling other features
The following may also be disabled:
All installed expansion boards
Fire protection output (NEN 2535 mode only)
Fault warning output (NEN 2535 mode only)
To disable any of these options, press the General Disable button for more than
3 seconds, press the 1 and 3 buttons to select the option to be disabled (the
corresponding LED flashes), and then press Enter to confirm the disablement.
Disablement is indicated as follows:
General Disable LED: On steady.
Corresponding LED: On steady yellow.
To enable a disabled option, press the General Disable button for more than 3
seconds, press the 1 and 3 buttons to select the option to be enabled, and then
press Enter.
Note: Disabled expansion boards will not operate or indicate a fault if there is a
fire alarm.