1X-X3 Operation Manual 29
Regulatory information
European standards for fire control and indicating equipment
These control panels have been designed in accordance with European
Standards EN 54-2, EN 54-4, and EN 12094-1.
In addition, all models comply with the following EN 54-2 and EN 12094-1
optional requirements.
Table 6: EN 54-2 optional requirements
Description
Output to fire alarm devices [1]
Output to fire alarm routing equipment [2]
Delays to outputs
Total loss of power supply
Test condition
[1] Inputs and outputs on the optional 2010
-1-SB expansion I/O board do not
support the optional
requirement of EN 54
-2 clause 7.8 and should not be used for fire alarm devices.
[2] Requires installation of optional 2010-1-SB expansion board (not supplied).
Table 7: EN 12094-1 optional requirements
Description
Delay release of extinguishing agent
Indication of extinguishing agent flow
Monitor component status
Emergency hold device (mode A or B)
Manual mode
Trigger signals to equipment within the system
Trigger signals to equipment outside the system
Emergency abort device
Activate alarm devices with different signals
European standards for electrical safety and electromagnetic compatibility
These control panels have been designed in accordance with the following
European standards for electrical safety and electromagnetic compatibility:
• EN 62368-1
• EN 50130-4
• EN 61000-6-3
• EN 61000-3-2
• EN 61000-3-3