EasyManua.ls Logo

Armstrong G2D80CT - Combustion Air Quality and Venting; Venting System Requirements

Armstrong G2D80CT
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
# 45465K005
Page 6
Figure 7
Inlet Air Restrictor Plate
The inlet air restrictor plate must be installed in all
installations using inside air for combustion (non-direct vent).
Contaminated Combustion Air
Excessive exposure to contaminated combustion air will
result in safety and performance related problems. The
recommended source of combustion air is outdoor air.
However, the use of indoor air in most applications is
acceptable if the following guidelines are followed:
1. If the furnace is installed in a confined space, it is
recommended that the necessary combustion air
come from the outdoors by way of an attic, crawl
space, air duct, or direct opening.
2. If indoor combustion air is used, there must be no
exposure to the substances listed in item 5.
3. All provisions for indoor combustion air must meet the
requirements for combustion air indicated in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54
(latest edition), and/or any applicable local codes. In
Canada, see CSA B149.1, Natural Gas and Propane
Installation Codes (latest edition).
4. The following types of installation may require out-
door air for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
5. Exposure to the following substances in the combustion
air supply may also require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine-based swimming pool chemicals
Water softening chemicals
Deicing salts or chemicals
Carbon tetrachloride
Halogen-type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Chlorinated laundry products
Hydrochloric acid
Venting
This furnace has a fan-assisted combustion system designed
for vertical venting into a suitable chimney or listed gas vent,
and is classified as a Category I furnace (negative vent) as
shipped from the factory. This furnace is dual certified as a
direct vent using outside air for combustion or it can use air
from inside the structure. See Figures 14 – 16 on pages 11
and 12 for optional outside combustion air applications.
The furnace is shipped with the air inlet pipe terminated to
the top panel for either inside or outside combustion air. An
inlet air restrictor plate (see Figure 7) is supplied with this
furnace and can be found in the plastic bag containing these
Installation Instructions and the User’s Information Manual.
For installations using inside air for combustion, the inlet air
restrictor plate must be installed as shown in Figure 8. Two
different sized inlet restrictor plates are supplied with the
furnace (2" and 3"). The 3" restrictor plate should be used
with non-direct vented 100K and larger models only; all
other non-direct vented models use the 2" restrictor plate.
Figure 6
Equipment in Confined Space
All Air from Outside
(All Air Through Horizontal Ducts)
Chimney or
Gas Vent
Furnace
Water Heater
Outlet Air
Inlet Air
Note: Each air duct opening shall have a free area of at least one
square inch per 2000 BTU per hour of the total input rating of
all equipment in the enclosure. If the equipment room is
located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall
have a free area of at least one square inch per 4000 BTU
per hour of the total input rating of all other equipment in the
enclosure.

Related product manuals