Common Faults
H C
Problem: “Blend temperature rises when system is in zero demand...”
Check blend circuit ow rate.
Flow rate is less than 19 l/m. Reset circuit ow
rate and check for the following:
• Air locks
• Blocked strainers
• Closed valves
• Pump failure
Water pressure
Make sure supply pressures are balanced.
Make sure mixed return is owing correctly to
hot water supply inlet.
Checkvalves
Check circuit to make sure checkvalves are
correct positioned and operating normally.
(See Piping Diagrams on pages 12 - 15).
Check mixed return temperature.
Minimum recirculation loop temperature loss
= 1°C
DRV40 display errors
These are the most likely error messages
to be displayed during this problem. For
the most probable causes and solutions
see DRV40 Display Errors on page 59.
If any other error message is displayed see DRV40 Display Errors on pages 58-60.