51
Alarm
Number
Alarm type
Description
0x400000
Range error
An illegal value was detected for one or more of
the following quantities during data acquisition:
Calibration constants, balance values,
admittance, estimated physical parameters
0x800000
Frequency range
(CHECK MOTOR and LEARN only). The measured
frequency differed from the nominal value.
During the learning period, eMCM learns the
motor only at the dominant frequency. In
inverter driven systems, it is important to set the
nominal frequency to this dominant frequency
otherwise, eMCM may never complete the
learning period. This condition is relaxed during
normal monitoring (IMPROVE and UPDATE)
where unlearned frequencies are updated
automatically
0x1000000
Frequency tolerance
Illegal value for the mean frequency (IMPROVE,
UPDATE and
MONITOR)
0x2000000
Noisy data
The estimated admittance is inconsistent with
the measured RMS values for voltage and
current. This usually indicates excessive noise in
the data
1.3 Warning Conditions
Warning
Number
Warning Type
Description
0x01
Test frequency
range
(MONITOR, IMPROVE, UPDATE only) The
measured frequency was different than (i.e.
outside the threshold of) the LEARN frequency
0x02
Residual error
An unexpectedly large value was calculated for
the modeling error. This is generally an indication
of an unstable line condition and will usually pass
0x04
Data size reset
Values for some quantities were checked and
found to be outside their allowable limits. The
values were reset to the upper or lower limits
0x08
Phase ordering
Phase ordering is different from the values set
0x10
Unstable system
Instability was detected for the system