EasyManuals Logo
Home>Asco>Control Unit>Aseptic Positioner D Series

Asco Aseptic Positioner D Series User Manual

Default Icon
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
503543-001
2
General installation and maintenance instructions
Valves with Positioner
D
- Series Aseptic
2
1
P
(2)
(1)
3
P
(2)
(1)
2
1
GB
All screw terminals must be properly tightened prior to op-
eration (be sure to observe a tightening torque of 3 Nm).
The electrical connection is made by a metal cable gland
M16 x 1,5 mm for cable dia. 4,5-9 mm (tightening torque: 3 Nm).
Put the cover and its seal back in place (be sure to observe
a tightening torque of 5 Nm).
2) Connection by M12 connector:
Pin
5
41
32
Single loop Double loop
1 + 24V
2 + Setpoint
3 GND
4 Disc position feedback External sensor input
5 ON/OFF output: 24 V PNP
Positioner
D
, single loop
terminal block
M12
5
41
32
1 + 24 V DC supply 1
2 GND supply 3
3 + Setpoint (0-10 V or 4-20 mA) 2
4 Setpoint GND 3
6 Disc position feedback 4
7 ON/OFF output: 24 V PNP 5
Positioner
D
, double loop
terminal block
M12
5
41
32
1 + 24 V DC supply 1
2 GND supply 3
3 + Setpoint (0-10 V or 4-20 mA) 2
4 Setpoint GND 3
5 External sensor input 4
7 ON/OFF output: 24 V PNP 5
PUTTING INTO OPERATION
Valve installation: See I&M sheets for the series Aseptic 2/2
valves (http://www.asconumatics.eu).
Positioner
D
unit characteristics:
- Pilot fluid: Air or inert gas, filtered 50 µm, unlubricated,
condensate-free and water-free (
- Supply pressure: 4 to 8 bar
-Ambientandpilotuidtemperature:0to+50°C
- Electrical protection: IP66 (EN 60529)
Analog setpoints to be selected when ordering:
- Voltage setpoint 0 – 10 V (200 k input resistance)
- Current setpoint 4 - 20 mA (250 input impedance)
- Supply voltage: 24 V DC ±10%
- Power rating: max. 8,5 W
- Hysteresis: < 2% of max. disc stroke
- Accuracy: < 2% of max. disc stroke
- ON/OFF output: 24 V PNP /max. 500 mA
-External sensor signal (option) = setpoint signal (0-10 V or
4-20 mA)
-Disc position feedback signal = setpoint signal (0-10 V or
4-20 mA)
PNEUMATIC CONNECTION (Fig. 5)
Connection: G 1/8 at pressure inlet.
Fig. 5
MANUAL OPENING AND CLOSING
It is possible to manually open and close the valve during
normal operation.
Procedure:
1 – Remove the cover.
2 To switch to manual mode, simultaneously press the “Open”
button (no. 3) and the “Close” button (no. 4) until the green
LED flashes.
3 – Press the top button to open: The valve will open as
long as the button is pressed, it will stop opening as
soon as the button is released (fig. 7).
Fig. 6 Fig. 7
Or,
Press the bottom button (no. 4) to close: The valve will close
as long as the button is pressed, it will stop closing as soon
as the button is released. (fig. 7)
You can:
- Obtain information on the disc’s position with a voltmeter or
an amperemeter connected to pins 2 and 6.
Exit from the manual mode:
- To exit the manual mode, again simultaneously press buttons
nos. 3 and 4 for 3 to 5 seconds; the disc will automatically
be restored into the setpoint position.
POSITIONER
D
UNIT REPLACEMENT
1- Removal of the unit to be replaced (fig. 8)
a. Disconnect and remove all electrical and pneumatic sup-
plies.
b. Disconnect the pneumatic connection to the valve and
remove connector no. 5 (not supplied in the kit).
c. Loosen screw F by several turns to remove the unit from
its support.
d.Removetheunit+stemassemblyandtakecaretoprotect
the stem against damage and bending stress.
e. Remove pneumatic supply connections nos. 5 and 6.
Fig. 8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Asco Aseptic Positioner D Series and is the answer not in the manual?

Asco Aseptic Positioner D Series Specifications

General IconGeneral
BrandAsco
ModelAseptic Positioner D Series
CategoryControl Unit
LanguageEnglish

Related product manuals