Ascon Tecnologic - K Series - ENGINEERING MANUAL - Vr. 9.0 PAG. 9
[15] o2F - Out 2 function
Available: When the instrument has out 2 option.
Range: nonE = Output not used. With this setting, Out 2
status can be driven directly from serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Timer output;
t.HoF = Timer out - OFF in Hold;
P.End = Program end indicator;
P.HLd = Program hold indicator;
P. uit = Program wait indicator;
P.run = Program run indicator;
P.Et1 = Program Event 1;
P.Et2 = Program Event 2.
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, burn out and Power Failure
indicator;
diF1 =
The output repeates the digital input 1 status
;
diF2 =
The output repeates the digital input 2 status
;
St.By = Stand By status indicator;
on = Out 2 forced to ON.
For other details see [12] O1F parameter.
[16] o2.AL - Alarms linked up with Out 2
Available: When [15] o2F = AL.
Range: 0... 31 with the following rule:
+1 = Alarm 1;
+2 = Alarm 2;
+4 = Alarm 3;
+8 = loop break alarm;
+16 = Sensor break (burn out).
For more details see [13] o1.AL parameter
[17] o2Ac - Out 2 action
Available: When [15] o2F is different from nonE.
Range:
dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with reversed LED indication;
rEU.r =
Reverse action with reversed LED indication.
For more details see [14] o1.Ac parameter.
[18] o3F - Out 3 function
Available: When the instrument has out 3 option
Range: nonE = Output not used. With this setting, Out 3
status can be driven directly from serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Timer output;
t.HoF = Timer out - OFF in Hold;
P.End = Program end indicator;
P.HLd = Program hold indicator;
P. uit = Program wait indicator;
P.run = Program run indicator;
P.Et1 = Program Event 1;
P.Et2 = Program Event 2.
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, burn out and Power Failure
indicator;
diF1 =
The output repeates the digital input 1 status
;
diF2 =
The output repeates the digital input 2 status
;
St.By = Stand By status indicator;
on = Out 3 forced to ON.
For other details see [12] O1F parameter.
[19] o3.AL - Alarms linked up with Out 3
Available: When [18] o3F = AL.
Range: 0... 31 with the following rule:
+1 = Alarm 1;
+2 = Alarm 2;
+4 = Alarm 3;
+8 = loop break alarm;
+16 = Sensor break (burn out).
For more details see [13] o1.AL parameter
[20] o3Ac - Out 3 action
Available: When [18] o3F is different from nonE.
Range: dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with reversed LED indication;
rEU.r =
Reverse action with reversed LED indication.
For more details see [14] o1.Ac parameter.
[21] o4F - Out 4 function
Available: When the instrument has out 4 option
Range:
nonE = Output not used. With this setting, Out 4
status can be driven directly from serial link;
H.rEG = Heating output;
c.rEG = Cooling output;
AL = Alarm output;
t.out = Timer output;
t.HoF = Timer out - OFF in Hold;
P.End = Program end indicator;
P.HLd = Program hold indicator;
P. uit = Program wait indicator;
P.run = Program run indicator;
P.Et1 = Program Event 1;
P.Et2 = Program Event 2.
or.bo = Out-of-range or burn out indicator;
P.FAL = Power failure indicator;
bo.PF = Out-of-range, burn out and Power Failure
indicator;
diF1 =
The output repeates the digital input 1 status
;
diF2 =
The output repeates the digital input 2 status
;
St.By = Stand By status indicator;
on = Out 4 forced to ON.
For other details see [12] O1F parameter.
[22] o4.AL - Alarms linked up with Out 4
Available: When [21] o4F = AL.
Range: 0... 31 with the following rule:
+1 = Alarm 1;
+2 = Alarm 2;
+4 = Alarm 3;
+8 = loop break alarm;
+16 = Sensor break (burn out).
For more details see [13] o1.AL parameter
[23] o4Ac - Out 4 action
Available: When [21] o4F is different from nonE.
Range:
dir = Direct action;
rEU = Reverse action;
dir.r = Direct action with reversed LED indication;
rEU.r =
Reverse action with reversed LED indication.
For more details see [14] o1.Ac parameter.